KNX Modbus TCP Gateway 716 secure

KNX Modbus TCP Gateway 716 secure

The KNX Modbus TCP Gateway 716 secure is a compact gateway between KNX TP and modbus TCP with 250 freely configurable datapoints.

The device enables easy integration of modbus devices that support the TCP protocol via IP and can act as a modbus master or slave. As master the device can address up to 5 slave devices.

The assignment between KNX objects and modbus registers can be configured via parameters in the ETS without an additional tool.

Two buttons and three LEDs allow local operation and visualization of the device status.

Furthermore, the device can be used as a programming interface to connect one or more PCs to the KNX bus (e.g. for ETS®).

Power is supplied via the KNX bus.
The device supports KNX Security.

Wz Schema Knx Modbus Tcp Gateway 716 2024 06 13 003

KNX Modbus configuration

The assignment between KNX objects and Modbus registers is made via parameters in the ETS – no further tool is required. 

The device enables the interpretation and scaling of the Modbus data according to the data point types of the KNX standard.
Two buttons and three multi-colored LEDs on the front panel allow local operation (test functions) and visualization of the device status.

Screenshot Ets 716 En 2021 03 15

Weinzierl Modbus Gateway Config Tool

Weinzierl_DCA_Modbus_Config_Tool_Image_EN

The Weinzierl Modbus Gateway Config Tool is a so-called DCA (Device Configuration AddIn) for the ETS. With this it is possible to export the configuration of a Weinzierl KNX Modbus TCP Gateway 716 database and import it into another gateway. The Weinzierl Modbus Gateway Config Tool is available online as a free download in the KNX Association online store under Shop / ETS Apps (creating a user account is necessary).

After adding it to the shopping cart and checking it out, the download link for the Weinzierl Modbus Gateway Config Tool will appear within a short time under “My account / Products”.

Please note: The Weinzierl Modbus Gateway Config Tool requires a commercial license of ETS 5.5 or higher.

Example configurations for use with the DCA can be found here.

ManufacturerDescriptionNameDownload
Alfen Wallbox Eve Single S LineZip
Fronius Hybrid inverter Symo Gen24 PlusZip
Huawai Hybrid inverter SUN2000Zip
iDM Heat pumpZip
Kaco Hybrid inverter Powador 18_0 TL3Zip
Kamstrup Heat meter Multical 603Zip
Producal GatewayWireless Proxima Base Station WBUZip
SenerTec Fuel cell Dachs 0.8Zip
Siemens Energy meter SentronZip
Stiebel Heat pump EltronZip
Sunspec Model 111Zip
Tecalor Heat pumpZip
Varta Energy storage Element Backup S5Zip

In order to further expand our offer of successfully tested configurations, we are pleased to receive such DCA files at any time.
You are welcome to send these DCA files with the manual of the Modbus device and register description to support@weinzierl.de.

Technical data

Mechanical Data

  • Housing: plastic
  • DIN rail mounted device, width: 1 unit (18 mm)
  • Weight: approx. 40 g

Indicators

  • 2 buttons and 3 LEDs (multicolor)
  • KNX programming button with LED (red)

Modbus

  • Type: TCP, Master or Slave
  • As master: up to 5 slave devices
  • Up to 250 data points

KNX

  • Medium TP
  • KNX Security
  • Interface protocol: cEMI
  • Support of KNX long frames
  • Device model: System B
  • Up to 8 KNXnet/IP Tunneling connections simultaneously

Internet protocols:

  • ARP, ICMP, IGMP, UDP / IP
  • TCP / IP, DHCP, Auto IP
  • KNXnet/IP Tunneling
  • Modbus TCP

Power supply

  • KNX Bus approx. 20 mA

Connectors

  • Bus connector for KNX (red / black)
  • LAN RJ-45 socket